S&P SISTEMAS DE VENTILACIÓN, S.L.U.
Llevant, 4
Polígono Industrial Llevant
08150 Parets del Vallès
Barcelona – Spain
consultas[zav]solerpalau[teč]com
www.solerpalau.com/en-en/home
Product description
Casing
is designed for horizontal exhaust of air. The fan base is made of galvanised sheet steel; the brackets, grille and screws are also galvanised. The cover and fan housing are made of aluminium sheet. The fan motor is mounted in the airflow. Protective grille to prevent contact.
Impeller
is radial with backward-curved blades. It is made of galvanised steel sheet and is statically and dynamically balanced.
Motor
is a special DC EC motor with an external rotor, designed for a supply voltage of 230 V/50 Hz (CRHB) or 400 V/50 Hz (CRHT). Continuous operating temperature: -20 to +40 °C. Ball bearings with lifetime grease lubrication. Protection rating: IP44 (CRHB) or IP54 (CRHT).
Direction of rotation
is possible in one direction only, as indicated by the arrow on the fan housing. The fan control does not allow the direction of rotation to be changed.
Terminal block
with a test switch is located on the fan housing. The internal terminal block has connection terminals for speed control, sensor-controlled regulation, and for setting and reading operating values. The protection rating is IP55.
Speed control
The fan can be operated in 4 basic modes, which can be selected using the switches on the control unit’s circuit board. The first mode maintains a constant pressure in the ducting based on the integrated sensor. The other modes allow for continuous automatic regulation to a constant air flow rate, a proportional mode, or a ventilation mode with two selectable operating characteristics: min./max. The control unit allows the connection of signals from external devices (CO2 sensors, temperature and relative humidity sensors), and an external
pressure sensor with a transducer and a 0–10 V or 4–20 mA output. The control system supports Modbus-RTU control. The Ecowatt Plus SPCM-WS module allows you to connect a smartphone to Wi-Fi and easily configure the fan via a web application. The module is not included in the scope of delivery.
Variants
CRHB/T-N1 Ecowatt Plus – the system is based on the use of modern components for DCV systems (demand-controlled ventilation). These are fans with microprocessor control, a built-in differential pressure sensor, an EC motor (electronically commutated), electrically operated exhaust disc valves, CO2 sensors, relative humidity sensors, and programmable timers for controlling the exhaust disc valves.
CRHB/T-N Ecowatt – a simpler version of the fan with an EC motor; the fan does not include a control module for constant pressure or flow. The fan is controlled solely by a 0–10 V control voltage.
Noise
emitted by the fan is specified in the tables. The values are measured at a distance of 4 m on the discharge side in a horizontal direction.
Note
Please enquire about permitted combinations of electrical accessories.
Commissioning
Expert assistance is available for the installation and commissioning of this product.
Parameters
| Základní údaje | |
|---|---|
| Motor type | EC |
| Mounting | Roof |
| Fan type | radial |
| Exhaust gas | horizontální |
| Připojení | |
| Connection pipe diameter | 400 mm |
| Elektrické parametry | |
| Power supply | 230 V |
| Ingress Protection | IP44 |
| Maximum power | 861 W |
| Maximum current | 3,60 A |
| Další | |
| Max. air temperature | 40 °C |
| Weight | 35,00 kg |
| Maximum speed | 1 400 min⁻¹ |
| Doplňkové parametry | |
| Ball bearings | Ano |
| Operations at COP | Yes |
| Operations at CAV | Yes |
| Modbus RTU | Yes |
Adherence to these instructions should not pose any safety, health or environmental risks in accordance with EC directives (CE marked). The same applies to other products used in the device or during installation. Consider the following warnings:
• Observe the safety instructions to prevent damage to the device or personal injury.
• The technical information in this manual must not be changed.
• It is forbidden to interfere with the motor of the device.
• In order for the device to comply with EC directives, the device must be connected to the mains in accordance with the applicable regulations.
• The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving part and / or live part.
• The device complies with the applicable regulations for the operation of electrical equipment.
• Always disconnect the device from the power supply before carrying out any work on it.
• Appropriate tools must be used when handling or maintaining the device.
• The device must only be used for the purposes for which it is intended.
• This appliance is not intended for use by children under 8 years of age and persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a responsible person. The user must ensure that children do not play with the device. Cleaning and maintenance of the appliance must not be carried out by children without supervision.


Share on Facebook
Tweet
Send email