Cabinet
The 45 mm thick wall panels are made of galvanized steel sheet with external painting in RAL 9002. The panels are internally filled with sound and thermal insulation made of non-combustible glass mineral wool. For ease of servicing, the unit cabinet is equipped with removable doors with locks. The unit frame is made of aluminium profiles, the wall panels are screwed into the frame. The water heater connections are routed to the outer casing of the unit. The cabinet is fitted with 4 hinges with Ø 12 mm holes for underfloor mounting of the unit.
Fans
The unit is fitted with a fan with backward curved blades, the impeller is made of composite material. The impeller is statically and dynamically balanced.
Motors
An EC motor is directly mounted on the fan impeller. The fan motor can be continuously controlled by an external 0...10 V or PWM signal. The motor is equipped with its own built-in thermal protection. The electric motor is IP44 rated.
Heaters
The water heaters are designed for a heating water temperature gradient dT = 20 K (80/60 °C) for an inlet air temperature te = -12 °C/90 % r.v. at nominal air flow. Electric heaters are designed for an inlet air temperature te = -12 °C/90% r.h. at nominal air flow and are equipped with an operating and emergency thermostat.
Filters
The unit contains one or more filter elements of filtration class F7 (optional filter class G4 to F9), which are situated in one filter wall. The filter is made of polypropylene filter material. Access to the filters is via the inspection door on the service side of the unit. In case of multi-stage filtration, the unit can be supplemented with MFL filter cartridges with MFR filter inserts, which are designed for installation in pipes.
Electrical connection
The supply voltage of the units is 1 × 230 V / 50 Hz or 3 × 400 V / 50 Hz and depends on the equipment of the unit. Supply cables, cables to sensors, power cables to fans are fed into the unit via plastic grommets in the unit wall, which are not included in the unit delivery. The electrical heater terminal block on RME units is accessible by removing the outer cover. The electric fan motor has the supply power cable routed to a plastic terminal box located inside the unit.
Regulation
The unit is supplied without regulation as standard. If required, the unit is equipped with Digireg® regulation. In case the unit is equipped with a MaR system directly from the factory, all sensors and actuators are electrically connected and tested. The control box is placed on the wall of the unit according to the actual space requirements of the specific project (the location of the MaR control box must be specified in the order).
Mounting
is possible in horizontal position with the service side from the side of the unit (marked in unit code H2) or from the bottom of the unit (marked in unit code H1). It is also possible to distinguish between right (P) and left (L) versions according to the position of the water heater outlets or the position of the electric heater connection terminal (for sizes 2400, 3000, 4000, 6000). The L or P position is determined by looking at the front inlet face of the heater in the direction of air flow. A handling area is required next to the unit for removing the lid and filters and for making periodic electrical inspections.
Noise
The sound power levels shown in the tables represent the intake and discharge sound power levels of the unit with A-weighted filter correction.
Variants
- RME with built-in electric heater and filter
- RMW with built-in water heater and filter
- RMK with filter without heater (on request)
Information
The unit is designed for ventilation of commercial premises. The delivery of the unit to the outdoor environment should be consulted.
Warranty Terms
The RME, RMW, RMK Ekonovent® equipment including the DVAV, DCAV and DCOP control system must be commissioned solely by the Seller or a person designated by the Seller to do so. Failure to comply with this condition shall result in the termination of the Buyer's rights under the defective performance and the Quality Warranty. Further conditions are set out in the Seller's Complaints Procedure.
Adherence to these instructions should not pose any safety, health or environmental risks in accordance with EC directives (CE marked). The same applies to other products used in the device or during installation. Consider the following warnings:
• Observe the safety instructions to prevent damage to the device or personal injury.
• The technical information in this manual must not be changed.
• It is forbidden to interfere with the motor of the device.
• In order for the device to comply with EC directives, the device must be connected to the mains in accordance with the applicable regulations.
• The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving part and / or live part.
• The device complies with the applicable regulations for the operation of electrical equipment.
• Always disconnect the device from the power supply before carrying out any work on it.
• Appropriate tools must be used when handling or maintaining the device.
• The device must only be used for the purposes for which it is intended.
• This appliance is not intended for use by children under 8 years of age and persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a responsible person. The user must ensure that children do not play with the device. Cleaning and maintenance of the appliance must not be carried out by children without supervision.