THGT/2-400-6/-1,1-L IP55 axial smoke extract fan

Fire ducted axial flow fans are advantageous due to their high flow rate and meet the requirement for heat and smoke extraction (OTC).
Read more
price on request
Availability: on request [13.8.2025, 00:00] Update
Goods cannot be ordered online.
Contact our sales specialists
or visit our branches.

Insert into the design HVAC program

Product code:
Manufacturer: S&P SISTEMAS DE VENTILACIÓN, S.L.U.   Read moreRead less

S&P SISTEMAS DE VENTILACIÓN, S.L.U.
Llevant, 4
Polígono Industrial Llevant
08150 Parets del Vallès
Barcelona – Spain
consultas[zav]solerpalau[teč]com
www.solerpalau.com/en-en/home

Product description
Cabinet

is welded from corrosion-resistant steel sheet with hot-dip galvanized surface, with flanges for connection to the circular pipe. The fan is certified according to EN 12 101-3 as suitable for heat and smoke extraction.

Running wheel

is made of Al alloy and is statically and dynamically balanced. From size 710 with steel hub. The impeller blade angle adjustment is made by the manufacturer, possible angles of rotation are indicated in the performance characteristics.

Motor

is asynchronous with short armature. The motors are 3-phase for 230/400 V up to 3 kW and 3-phase for 400 V for higher outputs and two-speed motors. Operating temperature for ventilation up to 40 °C, in case of fire according to classification F400(120), on request F300 / F200 (120). Motor protection IP55, insulation class H. Efficiency class IE3.

Clamps

Internal as standard for short enclosure, external for long enclosure. External terminal block for short enclosure and service door for long enclosure available on request.

Speed control

Fan control is not possible in the case of smoke and heat extraction. In operation ventilation mode, regulation is possible by frequency converter. Please observe the data on the motor label.

Flow direction

is standard from impeller to motor (i.e. direction B, from motor to impeller is direction A).

Instructions

The fans are suitable for air handling applications and are preferably used where high flow rates are required from the fans and where the fan function for heat and smoke removal is also a requirement.

Highlights

All manufacturer's recommendations must be followed during installation and design and are consistent with TGT axial fans in terms of performance.

Full description
Safety regulations

Adherence to these instructions should not pose any safety, health or environmental risks in accordance with EC directives (CE marked). The same applies to other products used in the device or during installation. Consider the following warnings:

• Observe the safety instructions to prevent damage to the device or personal injury.
• The technical information in this manual must not be changed.
• It is forbidden to interfere with the motor of the device.
• In order for the device to comply with EC directives, the device must be connected to the mains in accordance with the applicable regulations.
• The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving part and / or live part.
• The device complies with the applicable regulations for the operation of electrical equipment.
• Always disconnect the device from the power supply before carrying out any work on it.
• Appropriate tools must be used when handling or maintaining the device.
• The device must only be used for the purposes for which it is intended.
• This appliance is not intended for use by children under 8 years of age and persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a responsible person. The user must ensure that children do not play with the device. Cleaning and maintenance of the appliance must not be carried out by children without supervision.

Contact Us