MDF30 EURO 1050x550 PITZN fire dampers for square pipe

Square fire dampers serving as a closure of air ducts in case of fire.
Read more
B2B clients will see their prices after logging in
8 446,00 CZK excl. VAT
10 219,66 CZK incl. VAT
Availability: on request [19.8.2025, 16:10] Update
Goods cannot be ordered online.
Contact our sales specialists
or visit our branches.

Product code: BR332110565
Product description
Description

The MDF30 EURO square fire dampers are used as a closure for air ducts in case of fire. When the damper is closed, the spread of fire and the spread of smoke through the pipe from one fire section to another is prevented. Activation of the damper in case of fire is ensured by a 72 °C thermal fuse as standard (95 °C on request). Closure of the damper after activation of the thermal fuse is ensured by a mechanism fitted with a closing spring. The damper shell is made of two parts made of galvanised steel sheet, separated by a calcium silicate plate to prevent heat transfer. It is fitted with two inspection holes. The flap sheet is made of calcium silicate plates. The blade rotates on steel pins mounted in bronze bushings. The flapper is fitted with a limit switch (CLOSED). The flapper is designed with minimum pressure loss in mind. The damper is provided with a flange at both ends for connection to the air piping.

Features

CE marking according to EN 15650 certification, classification according to EN 13 501-3 is EI 90/120 S. Tested according to EN 1366-2 at 500 Pa.

Use

The flaps are suitable for installation in all common building structures such as rigid wall structures, lightweight partitions or rigid ceiling structures. The flap can be installed in fire separating construction with the axis of the sheet vertically or horizontally. Fire dampers can only be used for air free of mechanical and chemical impurities. Maximum flow velocity 10 m/s.

Mounting

The fire dampers are designed for square air ducts from 200x200 mm to 1500x800 mm (width x height). The axis of the damper must be inside the fire separation structure.

Notice

Fire dampers are dedicated fire-safety devices (see the Ministry of the Interior Decree on fire prevention), therefore it is necessary to follow the prescribed rules (training of installers, regular operational checks, etc.). Ask for information!

Accessories

- ME40 microswitch for signalling "closed" or "open" damper
- KS1 brackets for ceiling installation
- KS2 brackets for light partition installation
- FS31100 thermal fuse 95 °C
- RDH pipe inspection element

Full description
Safety regulations

Adherence to these instructions should not pose any safety, health or environmental risks in accordance with EC directives (CE marked). The same applies to other products used in the device or during installation. Consider the following warnings:

• Observe the safety instructions to prevent damage to the device or personal injury.
• The technical information in this manual must not be changed.
• It is forbidden to interfere with the motor of the device.
• In order for the device to comply with EC directives, the device must be connected to the mains in accordance with the applicable regulations.
• The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving part and / or live part.
• The device complies with the applicable regulations for the operation of electrical equipment.
• Always disconnect the device from the power supply before carrying out any work on it.
• Appropriate tools must be used when handling or maintaining the device.
• The device must only be used for the purposes for which it is intended.
• This appliance is not intended for use by children under 8 years of age and persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a responsible person. The user must ensure that children do not play with the device. Cleaning and maintenance of the appliance must not be carried out by children without supervision.