BX-1H 160 fire valve

Fire protection disc valve designed for use as a fire stop in ventilation systems.
Read more
B2B clients will see their prices after logging in
3 115,00 CZK excl. VAT
3 769,15 CZK incl. VAT
Availability: on request [23.8.2025, 04:10] Update
Goods cannot be ordered online.
Contact our sales specialists
or visit our branches.

Product code: GR102100030
Product description
Description

The BX-1H Fire Plate Valve is made of painted steel plate. The valve consists of a circular shell, a control disc, a mounting sleeve and a seal to provide inherent fire and smoke resistance. The control disc of the valve allows easy flow control and positioning by means of a counter-nut.

Use

The BX-1H fire valve is designed for installation in a vertical fire partition. The valve can be placed at the beginning of the pipe route. In the event of a fire, the valve closes and separates adjacent fire compartments. The valve closes when the temperature of the passing air exceeds 72 °C. Its function is to prevent further spread of the fire. In the operating position, the valve is in the open position (stand-by position).
The BX-1H fire valves are classified according to EN 13501-3+A1:2010 as EI 60 (in o->i) S. The valve design complies with EN 15650:2010.

Accessories

- 1WKP limit switch for the "open" position
- 1WKK limit switch for the "closed" position
- 1WKKP limit switches for the "open" and "closed"
- 1WKKP limit switches for the "open" and "closed"
- KM35 mounting sleeve L = 35 mm
- KM67 mounting sleeve L = 67 mm
- KM120 mounting sleeve L = 120 mm
- KM150 mounting sleeve L = 150 mm

Mounting

- the valve is designed for air extraction, at the beginning of the extraction pipe route
- the product must be installed in accordance with the verified project documentation in terms of its classification - see Declaration of Performance
- the valve must be installed according to the enclosed installation instructions
- we recommend that it is installed in such a way that regular maintenance is possible as part of regular inspections

Caution

Fire valves are fire safety devices, therefore it is essential to comply with the rules prescribed by the standard (training of installers, carrying out regular operational checks, etc.). Ask for more information.

Full description
Safety regulations

Adherence to these instructions should not pose any safety, health or environmental risks in accordance with EC directives (CE marked). The same applies to other products used in the device or during installation. Consider the following warnings:

• Observe the safety instructions to prevent damage to the device or personal injury.
• The technical information in this manual must not be changed.
• It is forbidden to interfere with the motor of the device.
• In order for the device to comply with EC directives, the device must be connected to the mains in accordance with the applicable regulations.
• The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving part and / or live part.
• The device complies with the applicable regulations for the operation of electrical equipment.
• Always disconnect the device from the power supply before carrying out any work on it.
• Appropriate tools must be used when handling or maintaining the device.
• The device must only be used for the purposes for which it is intended.
• This appliance is not intended for use by children under 8 years of age and persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a responsible person. The user must ensure that children do not play with the device. Cleaning and maintenance of the appliance must not be carried out by children without supervision.