TGT axial fans

TGT axial fans are a powerful solution for applications with high airflows and medium pressure drops. They feature robust construction, energy-efficient IE3 motors, IP55 protection and a wide variety of designs. With a diameter range up to 1609 mm, they are ideal for industrial and commercial air handling systems.

Powerful solution for large air volumes

TGT fans are designed for facilities where high airflow is required while maintaining reliability, efficiency and long life. They are particularly suitable for industrial air handling, process ventilation and large building ventilation systems.

Wide range of sizes

The TGT range is available in 13 sizes with impeller diameters from 400 to 1609 mm:
400 / 450 / 500 / 560 / 630 / 710 / 800 / 900 / 1000 / 1120 / 1250 / 1409 / 1609 mm

This range allows precise selection of the fan according to the required performance and the parameters of the pipe network.

Optimized for power and pressure

Fans are designed for:

  • large airflows
  • medium pressure drops
  • stable and continuous operation

Robust design includes

Fan housing:

  • corrosion resistant steel plate
  • galvanized surface
  • Conversion: short or long cabinet (service door can be added on request for the long version)
  • flanges for circular pipes

Running wheel:

  • aluminium alloy (Al)
  • static and dynamic balance
  • blade angle adjustment by the manufacturer (18°-34°) according to the selected operating point
  • variants with 3 / 6 / 9 / 12 blades according to the working point

The result is quiet operation, high efficiency and reduced vibration.

Powerful motors

The TGT fans are equipped with asynchronous motors:

  • 3 phase design
  • voltage 230/400 V or 400 V
  • frequency 50 Hz
  • IP55 protection
  • Class F insulation
  • temperature range -20 to +40 °C
  • Efficiency class IE3

Speed control: Possible with frequency converter.

Variability of design

A wide range of variants is available:

  • short/long cabinet
  • external terminal blocks (CK, LK, LPK)
  • service door (long version)
  • selection of flow direction
  • other special configurations on request

ATEX design

For demanding environments, an explosion-proof version is also available
The ideal solution for a wide range of HVAC systems

Performance, assembly and installation

Operating parameters:

  • fan protection: IP55
  • max. air temperature: 40 °C
  • standard flow direction: from impeller to motor

Mounting and installation:

  • installation in any position
  • recommended with motor axis horizontal
  • flexible connection to pipe required
  • the housing must not transmit mechanical stress

Correct installation is essential for quiet operation and long life of the equipment.

TGT fans offer a combination

  • high performance
  • robust design
  • energy efficiency (IE3)
  • durability (IP55)
  • wide design variability
Contact Us