S&P SISTEMAS DE VENTILACIÓN, S.L.U.
Llevant, 4
Polígono Industrial Llevant
08150 Parets del Vallès
Barcelona – Spain
consultas[zav]solerpalau[teč]com
www.solerpalau.com/en-en/home
Product description
Cabinet
It is made of steel sheet, coated with black lacquer, the screws are electroplated.
Running wheel
is made of glass fibre reinforced thermoplastic. The impeller is statically and dynamically balanced.
Motor
is asynchronous, black lacquer finish, stator with cooling fins, thermal protection of windings, insulation class F, operating temperature -40 to +70 °C. HCFB fan motors are 1-phase for 230 V, HCFT are 3-phase for 230/400 V or 3-phase for 400 V. Ball bearings with grease packing for life. IP65 protection.
Speed control
is carried out by electronic or transformer regulators by changing the voltage, for 3-phase types by frequency converters.
Rotation direction
can be changed for both single-phase and three-phase motors. With a standard impeller, the flow rate drops by approx. 30% when the direction of rotation is reversed. With the wall-mounted version, the air flow from the motor to the impeller is standard.
Clamps
It is made of black plastic, single-phase design has a start-up capacitor. The terminal block is located on the motor (wall mounted version).
Mounting
Fan in each motor axis position. The enclosure must not transmit mechanical stresses from the building structures.
Noise
emitted by the fan is given in the tables, the measurements being made at a distance equal to three times the impeller diameter (but not less than 1,5 m) in the free acoustic field.
Parametry
| Základní údaje | |
|---|---|
| Fan type | Axial |
| Weight [kg] | 13,00 kg |
| Installation | Wall |
| Připojení | |
| Connection pipe diameter [mm] | 450 mm |
| Elektrické parametry | |
| Power supply [V] | 230 V |
| Ingress Protection | IP65 |
| Engine type | AC |
| Maximum power [W] | 103 W |
| Maximum current [A] | 0,70 A |
| Regulatability | Ano |
| Vybavení | |
| Ball bearings | Yes |
| Check valve | No |
| Delayed run-down | No |
| Adjustable coasting | No |
| Hygrostat | No |
| Motion sensor | No |
| Adjustability | No |
| Adjustability | No |
| Particle filter | No |
| More intake ports | No |
| Sound insulation | No |
| Další | |
| Max. air temperature [°C] | 70 °C |
| Maximum speed [min⁻¹] | 920 min⁻¹ |
Adherence to these instructions should not pose any safety, health or environmental risks in accordance with EC directives (CE marked). The same applies to other products used in the device or during installation. Consider the following warnings:
• Observe the safety instructions to prevent damage to the device or personal injury.
• The technical information in this manual must not be changed.
• It is forbidden to interfere with the motor of the device.
• In order for the device to comply with EC directives, the device must be connected to the mains in accordance with the applicable regulations.
• The device must be installed in such a way that under normal operating conditions it cannot come into contact with any moving part and / or live part.
• The device complies with the applicable regulations for the operation of electrical equipment.
• Always disconnect the device from the power supply before carrying out any work on it.
• Appropriate tools must be used when handling or maintaining the device.
• The device must only be used for the purposes for which it is intended.
• This appliance is not intended for use by children under 8 years of age and persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a responsible person. The user must ensure that children do not play with the device. Cleaning and maintenance of the appliance must not be carried out by children without supervision.