New version of the catalogue Mass ventilation of garages!
In the catalogue we present suitable fan types and possible ventilation methods for specific garage buildings.
The design method using Computational Fluid Dynamics (CFD) simulation software is commented on.
The catalogue can be downloaded here.

CVB/4-180/180-N-147W Centribox IP44 silent centrifugal fan

Sound-insulated radial ducted fans suitable for applications where low fan noise is advantageous - for ventilation of restaurants, sports halls, hospitals and warehouses.
Read more
B2B clients will see their prices after logging in
24 870,00 CZK excl. VAT
30 092,70 CZK incl. VAT
Availability: on request [27.4.2024, 16:10] Update

Insert into the design HVAC program

Product code: SP230100031
EAN: 8413893921765
Product description
Cabinet

is made of galvanized steel sheet. The cabinet is internally coated with a 7 mm layer of soundproofing material. The fan is mounted in the enclosure on sprung profiles to reduce vibration transmission. Circular sockets are screwed onto the housing for connecting flexible hoses or circular pipework. The cabinet is under vacuum when the fan is in operation.

Fan

is radial with forward curved blades, double-sided suction.

Motor

is asynchronous with short armature, mounted in the air stream. The motor has lifetime grease-filled ball bearings and a built-in thermal overheat protector. Class F insulation, IP44 protection. Operating temperature -20 °C to +40 °C.

Square box

It is made of black plastic as standard, is loosely connected to the supply cable from the motor and can be screwed to an easily accessible location on the enclosure with self-tapping screws. Cable length approx. 0.5 m, IP55 protection.

Noise

emitted by the fan is listed in the tables.

Mounting

is also possible outdoors with the use of a CSC canopy, preferably with the motor axis horizontal, taking into account the life of the bearings. Clearance must be left around the fan for removal of side panels and inspection work. The casing must not transmit mechanical stresses from the pipework. A flexible connection to the ductwork must be used.

Instructions

The fans are suitable for air handling applications where the low noise level of the fan is advantageous. The fans are particularly suitable for ventilation of restaurants, sports halls, hospitals and warehouses.

Full description
Downloads
Technical sheets, manuals and declarations
Catalogue sheet .pdf (238.96 kB)
Operating Instructions .pdf (186.79 kB)
Declaration of conformity .pdf (361.25 kB)
CAD files
2D .dwg (32.33 kB)
Contact Us